How to operate building services to prevent the spread of COVID-19 virus SARS-CoV-2

The following information is used for educational purposes only.

How to operate building services to prevent the spread of COVID-19 virus SARS-CoV-2

BY BIOENGINEER

March 19, 2020



Credit: TalTech


On March 17, Federation of European Heating, Ventilation and Air Conditioning Associations REHVA published guidance on the operation and use of building services in areas with a coronavirus disease (COVID-19) outbreak. Representing a network of more than 120.000 engineers from 27 European countries, REHVA guidance complements the general guidance for employers provided by WHO and is targeted to commercial and public buildings.

REHVA Research and Technology Committee chair, professor Jarek Kurnitski from Tallinn University of Technology: “Our document addresses the risk of airborne transmission through small particles

The document provides practical recommendations which cover ventilation system operation times, use of window airing, safe use of heat recovery sections, no use of recirculation in central ventilation systems as well as on the room level, and some explanation how to avoid overreactions which are easy to happen in situations with limited knowledge.

It is recommended to switch on ventilation systems a couple of hours earlier and also to extend the operation. Better solution is even to keep the ventilation on 24/7, possibly with lowered (but not switched off) ventilation rates when people are absent in order to remove virus particles out of the building. Exhaust ventilation systems of toilets should always be kept on 24/7, and make sure that negative air pressure is created, especially to avoid the faecal-oral transmission.

In buildings without mechanical ventilation systems it is recommended to actively use operable windows so that one could open windows for 15 min when entering the room especially when the room was occupied by others beforehand. Also, in buildings with mechanical ventilation, window airing can be used to further boost ventilation. Opening of windows in toilets should be generally avoided as this may cause a reverse direction operating ventilation and contaminated airflow from the toilet to other rooms.

Recirculation shall not be used, because virus particles in return ducts can re-enter a building in recirculation sectors of centralized air handling units. Thus, recirculation dampers have to be closed via the Building Management System or manually. When possible, decentralized systems such as fan coil units that use local recirculation, also should be turned off to avoid resuspension of virus particles at room level. Similarly to recirculation, heat recovery devices may carry over virus attached to particles from the exhaust air side to the supply air side. In rotary heat exchangers particles deposit on the return air side of the heat exchanger surface after which they might be resuspended when heat exchanger turns to the supply air side. Therefore it is recommended to (temporarily) turn off rotary heat exchangers during SARS-CoV-2 episodes.

It is also important to understand which actions have no practical effect and are not needed. Transmission of some viruses in buildings can be limited by changing air temperatures and humidity levels. In the case of COVID-19 this is unfortunately not an option as the SARS-CoV-2 virus is quite resistant to environmental changes and is susceptible only for a very high relative humidity above 80% and a temperature above 30 ?C, which are not attainable and acceptable in buildings for other reasons (e.g. thermal comfort). Thus, there is no need for humidification, and usually any adjustment of setpoints for heating or cooling systems is not needed. Similarly there is no need to replace outdoor air filters of the ventilation system, which are not a contamination source in this context. Room air cleaners can be useful in specific situations, but the floor area they can effectively serve is normally quite small, typically less than 10 m2. There have been overreactive statements recommending to clean ventilation ducts in order to avoid SARS-CoV-2 transmission via ventilation systems. Duct cleaning is not effective against room-to-room infection because the ventilation system is not a contamination source if given guidance about heat recovery and recirculation is followed.


COVID-19 – REHVA Guidance document: https://www.rehva.eu/activities/covid-19-guidance


Source:https://bioengineer.org/how-to-operate-building-services-to-prevent-the-spread-of-covid-19-virus-sars-cov-2/